Establishing business in South Korea during challenging phase of Worldwide Lockdown

Establishing business in South Korea during challenging phase of Worldwide Lockdown

PROJECT 

Supply, Installation and testing of Encon’s first Cooling Tower Fan assembly in South Korea.

CHALLENGE 

The year 2020 has been a challenging year marked by historical events and unforeseen changes to work lives. When the entire world was dealing with the Pandemic, we are no different. Though we have started our new business relation with one of the leading South Korean power sector, however due to worldwide travel restriction we were unable to depute our technician on site to provide assistance and support for installing Cooling tower fan assembly.

SOLUTION 

For installation and performance testing, we provide assistance to plant technician through video conference meetings and other online modes. In spite of onsite weather difference, our technicians and engineers have guided well to successfully install the Cooling Tower Fan and achieve the desired performance.

PERFORMANCE TEST AND RESULTS 

A performance evaluation test of cooling tower fan has been conducted by the client as per CTI PTG-143 to submit a detailed report which highlighted the excellent performance and power savings..

Fan Diameter

9144 mm

RPM

125

 

PARAMETERS

EXISTING ENCON SAVINGS
Volume flow rate m3/s 548 573.09 4.38%
Power kW 165.33 115.05 30.42%
SPL dB 76.95 75.05 -2.5%
Vibration 1.62 1.235 -23.7%